FRP Cooling Tower

HBLD-500 Industrial Cooling Tower Supplier | Direct Factory for HVAC & Power Plants

Share:

As a volume-manufacturing exporter based in Guangdong, we offer the HBLD-500 forced-draft cooling tower with modular casing panels that enable on-site assembly within 8 man-hours. This model excels in variable-flow applications, such as injection molding machine cooling and district heating return water quenching. Each unit undergoes a full-load noise test below 85 dBA at 10 meters, aligning with urban industrial park ordinances. We publish real-time factory inventory levels and provide a 3D BIM model for seamless integration into your existing piping network. For urgent project rollouts, we support letter of credit usance and split-shipping options, ensuring your construction timeline stays intact without capital tie-up. Our after-sales team offers remote vibration diagnostic support via IoT sensors, reducing unnecessary site visits.

Hebei Fortis Technology Co., Ltd Product Brochure

HBLD-500

Product Advantages

Backward-Curved Inlet Louvers That Reduce Pump Suction Cavitation
The air intake louvers are angled at 22° with a proprietary honeycomb mesh, which not only prevents sunlight algae growth but also straightens incoming airflow to reduce pressure drop across the fill pack by 15%. More importantly, this louver design minimizes vortex formation above the basin, ensuring a stable submergence depth of 18 inches at the pump suction nozzle. Field data shows 22% fewer cavitation-related impeller replacements on downstream pumps compared to towers with flat-bar louvers, extending your entire cooling loop’s MTBF (Mean Time Between Failures).

Off-the-Shelf Component Interchangeability for Global Supply Chains
All rotating parts—fan shafts, bearing housings, V-belt pulleys, and motor frames—follow ISO 286 standard fitments and IEC metric dimensions. Your local supplier in Europe, Southeast Asia, or the Americas can source replacement bearings (SKF/FAG equivalents) and belts (Optibelt/Gates) from regional distributors within 24 hours. We deliberately avoid proprietary odd-sized components, so you are never held hostage to single-source spares, even if our factory is at full capacity during peak seasons.

Factory-Matched Thermal Performance Curve with CTI Code Compliance
We do not supply generic selection charts. Each HBLD-500 is shipped with a unit-specific thermal performance certificate generated from our in-house CTI (Cooling Technology Institute) certified test station, calibrated against actual wet-bulb temperatures from 15°C to 32°C. The approval curve guarantees 100% of nominal capacity at 5°C range and 28°C inlet wet-bulb, with a tolerance of ±2%. This documentation is accepted by third-party engineering consultants and insurance underwriters, eliminating the need for costly on-site performance revalidation.

Parameter Specifications

FRP Fiberglass GFRP Square Low Noise Type Counterflow Cooling Tower

Product

 Square Cross Flow Cooling Tower

Model

τ=28℃
Coolable water volume(m³/h)△t=5℃

Main Dimensions (mm)  

Air Volume m³/h

Fan Diameter (mm)

Motor Installed Capacity (kw)

Weight (t)

τ=28℃
Coolable water volume(m³/h)△t=10℃

Noise at standard point
dB(A)

Total Height

Length×
Width

self-weight

operating weight

AHBLD/HBLD-300

300

4514

7250×

3810

167000

3400

7.5

5.85

13.38

/

59.0

AHBLD/HBLD-500

500

5230

8033×

4650

260000

4200

11.0

9.2

17.24

/

61.5

AHBLD/HBLD-700

700

5319

8930×

6640

370000

5000

18.5

12.95

26.05

/

62.6

AHBLCD/HBLCD-300

300

6230

10650×

3810

167000

3400

7.5

7.05

14.18

/

52.5

AHBLCD/HBLCD-500

500

7030

11640×

4650

260000

4200

11.0

10.8

18.84

/

53.7

AHBLCD/HBLCD-700

700

7180

12540×

6640

370000

5000

18.5

14.75

26.81

/

54.5

AHBLG/HBLG-300

/

4514

7250×

3810

200000

3400

11.0

6.13

13.66

300

64.5

AHBLG/HBLG-500

/

5230

8033×

4650

320000

4200

18.5

9.42

17.46

500

65.0

AHBLG/HBLG-700

/

5319

8930×

6640

450000

5000

30.0

13.19

26.29

700

66.0

The standard point noise is measured at a distance equal to the equivalent diameter of the air inlet window or its shield equivalent diameter, and 1.5 meters above the ground. The equivalent diameter Dₘis calculated by the formula: Dₘ= 1.13×Length×Width

Features

The FRP cooling tower serves not only as a temperature regulator but also delivers an efficient, durable, and maintenance-free solution with optimized lifecycle costs. By harnessing the unique properties of FRP materials, it fundamentally addresses the critical challenges of corrosion and lifespan limitations in harsh operating environments, making it the go-to choice for cooling systems in modern industrial and commercial facilities.

Application

 

Central air conditioning system: refrigeration station for commercial buildings, hotels and hospitals.

Industrial refrigeration: process cooling for food processing, chemical, pharmaceutical and plastic industries.

Power industry: auxiliary cooling system for thermal power plant and nuclear power plant.

Manufacturing industry: circulating water cooling for metallurgical and mechanical processing plants.

Data center: Provides cooling water for server rooms.

Payment

T/T, Western Union.

Service

Customize and design the size and style according to requirements

Related Products

Square Cross Flow HBLG-500 FRP Cooling Tower | Data Center & Industrial | Factory Export

Square Cross Flow HBLG-500 FRP Cooling Tower | Data Center & Industrial | Factory Export

Direct factory exporter of HBLG-500 square cross flow towers. UV-stabilized FRP body for data centers & chemical plants. Low pumping head, ISO export packing.

Stainless Steel Cooling Tower for HVAC & Industrial Process | Factory-Direct Export

Stainless Steel Cooling Tower for HVAC & Industrial Process | Factory-Direct Export

Direct from our ISO-certified factory: SUS304/316L stainless steel cooling towers engineered for corrosive environments & HVAC plants. Request export quote & specs.

Square Cross Flow FRP Cooling Tower for Industrial HVAC | China Supplier

Square Cross Flow FRP Cooling Tower for Industrial HVAC | China Supplier

Square cross flow FRP cooling tower built for industrial HVAC and light manufacturing. Low water quality tolerance, easy basin access, factory-direct pricing from China. Get specs.

FRP Integrated Cooling Tower for Chemical & HVAC | Factory Direct CE certificate

FRP Integrated Cooling Tower for Chemical & HVAC | Factory Direct CE certificate

Source directly from a China-based FRP cooling tower manufacturer. Corrosion-resistant integrated units engineered for chemical processing, data centers & HVAC. Request a factory quote.

Contact us immediately to discuss your product project requirements

Contact Us

Contact Us

Tel.: +86 189 3266 2725

E-mail: sale@hbfortis.com

Add.: No.8-1, Zhenxing Street, Matun Town, Zaoqiang County, Hengshui City, Hebei Province

Get in Touch

Get in Touch

Copyright © Hebei Fortis Technology Co., LTD All Rights Reserved | Sitemap | Privacy Policy | Powered by