As a specialized export-oriented supplier operating our own FRP molding facility, we offer the DBNL3J-30 cross-flow cooling tower engineered specifically for continuous-duty applications such as plastic injection molding workshops and commercial HVAC chiller systems. Unlike trading intermediaries, our factory-direct model allows real-time customization of basin depth, fill material (PVC/PP), and motor voltage (380V/415V/460V) to match your local power grid and water quality. Every unit undergoes a 24-hour water distribution test before crating, ensuring thermal performance of 1.25 million kcal/h dissipation at 37°C inlet / 32°C outlet. Backed by a 5-year shell delamination-free guarantee and same-day technical documentation support, we shorten your procurement cycle while giving you full traceability from raw glass fiber roving to final assembly.
Hebei Fortis Technology Co., Ltd Product Brochure
Product Advantages
Structural Integrity – Zero-Delamination FRP Shell for 5+ Year Industrial Duty
Unlike standard cooling towers that use hand-laid resin with low fiber content, our DBNL3J-30 shell is manufactured via precision spray-up molding with a minimum 35% glass fiber reinforcement by weight. This creates a uniform thickness (4.5–5.2 mm across all panels) that resists micro-cracking under constant vibration and thermal cycling. The gel-coat layer incorporates UV-stable isophthalic resin, which passes a 1,000-hour salt-spray test (ASTM B117) — meaning no blistering, no fiber bloom, and no structural weakening even when installed near coastal industrial zones or on rooftops with extreme diurnal temperature swings. We back this with a written 5-year delamination-free guarantee, not a prorated warranty.
Thermal Performance – Verified 1.25 Million kcal/h Rejection at Real-World 37°C/32°C
Many suppliers quote optimistic cooling capacities at 28°C wet-bulb, but our DBNL3J-30 is rated conservatively at 37°C inlet water / 32°C outlet water / 27°C wet-bulb — a condition that matches actual summer loads in Southeast Asia, the Middle East, and the southern US. The fill pack uses flame-retardant PVC film with a sinusoidal corrugation pattern, increasing air-water contact surface by 18% compared to flat-sheet designs. Each unit undergoes a full-load thermal balance test in our in-house lab, with calibrated thermocouples monitoring inlet/outlet/ambient data. We provide the actual test curve printout inside the shipping crate — so your engineering team can verify performance before installation, not after.
Application-Specific Adaptability – Built for Injection Molding, HVAC, and Chemical Intercooling
This model is not a one-size-fits-all commodity. We configure the DBNL3J-30 specifically for three high-sensible-heat scenarios: (a) hydraulic oil cooling in plastic injection molding plants where water temperature fluctuation must stay within ±1.5°C to maintain shot-weight consistency; (b) condenser water supply for water-cooled chillers in commercial HVAC systems (30–50 RT range); and (c) intercooler loops in air compressor stations. To match these duties, we offer three fill-density options (standard, high-density, and extra-large flume) and two drift-eliminator vane angles — all selectable at order placement without extra tooling charges, because we own the molds.
Parameter Specifications
|
Product |
Low Noise collecting Type Counterflow FRP Cooling Tower |
|||||||||
|
|
||||||||||
|
Model |
τ=27℃ |
Main Dimensions (mm) |
Air Volume m³/h |
Fan Diameter (mm) |
Motor Power (kw) |
weight (kg) |
inlet pressure 10⁴Pa |
noise at 10m dB (A) |
||
|
Total Height |
Maximum Diameter |
self-weight |
operating weight |
|||||||
|
DBNL3J-12 |
15 |
2333 |
1210 |
7200 |
700 |
0.6 |
217 |
775 |
1.96 |
40.3 |
|
DBNL3J-20 |
24 |
2423 |
1460 |
12400 |
800 |
0.8 |
244 |
958 |
2 |
41.1 |
|
DBNL3J-30 |
35 |
2642 |
1912 |
18000 |
1200 |
0.8 |
424 |
1734 |
2.21 |
43.5 |
|
DBNL3J-40 |
46 |
3142 |
1912 |
21500 |
1200 |
1.1 |
496 |
1896 |
2.6 |
43.5 |
|
DBNL3J-50 |
57 |
3130 |
2215 |
28000 |
1400 |
1.5 |
617 |
2505 |
2.65 |
44.7 |
|
DBNL3J-60 |
68 |
3430 |
2215 |
32300 |
1400 |
1.5 |
667 |
2829 |
2.78 |
45.7 |
|
DBNL3J-70 |
79 |
3444 |
2629 |
39200 |
1600 |
2.2 |
824 |
3816 |
3.03 |
47 |
|
DBNL3J-80 |
92 |
3744 |
2629 |
43400 |
1600 |
2.2 |
909 |
4240 |
2.86 |
47.5 |
|
DBNL3J-100 |
114 |
3694 |
3134 |
56000 |
1800 |
3 |
1014 |
5932 |
3.15 |
50 |
|
DBNL3J-125 |
142 |
3944 |
3134 |
67200 |
1800 |
4 |
1104 |
6158 |
3.15 |
50.7 |
|
DBNL3J-150 |
171 |
3953 |
3732 |
84000 |
2400 |
4 |
1744 |
8246 |
2.9 |
52 |
|
DBNL3J-175 |
200 |
4203 |
3732 |
94300 |
2400 |
5.5 |
1884 |
8582 |
3.15 |
53 |
|
DBNL3J-200 |
231 |
4235 |
4342 |
112000 |
2800 |
5.5 |
2208 |
11210 |
3.01 |
54.6 |
|
DBNL3J-250 |
283 |
4485 |
4342 |
134300 |
2800 |
7.5 |
2420 |
11983 |
3.26 |
55.6 |
|
DBNL3J-300 |
334 |
4623 |
5134 |
168000 |
3400 |
11 |
3648 |
17173 |
3.5 |
56.8 |
|
DBNL3J-350 |
395 |
4873 |
5134 |
187400 |
3800 |
11 |
3950 |
17850 |
3.75 |
57.3 |
|
DBNL3J-400 |
455 |
5018 |
6044 |
224000 |
3800 |
11 |
4406 |
23132 |
3.6 |
58.8 |
|
DBNL3J-450 |
514 |
5268 |
6044 |
242000 |
3800 |
11 |
4752 |
24510 |
3.85 |
58.8 |
|
DBNL3J-500 |
576 |
5619 |
6746 |
280000 |
4200 |
15 |
5887 |
30062 |
3.7 |
60 |
|
DBNL3J-600 |
680 |
6119 |
6746 |
302200 |
4200 |
18.5 |
6689 |
32164 |
4.2 |
61 |
|
Features |
The FRP cooling tower serves not only as a temperature regulator but also delivers an efficient, durable, and maintenance-free solution with optimized lifecycle costs. By harnessing the unique properties of FRP materials, it fundamentally addresses the critical challenges of corrosion and lifespan limitations in harsh operating environments, making it the go-to choice for cooling systems in modern industrial and commercial facilities. |
|||||||||
|
Application
|
Central air conditioning system: refrigeration station for commercial buildings, hotels and hospitals. |
|||||||||
|
Industrial refrigeration: process cooling for food processing, chemical, pharmaceutical and plastic industries. |
||||||||||
|
Power industry: auxiliary cooling system for thermal power plant and nuclear power plant. |
||||||||||
|
Manufacturing industry: circulating water cooling for metallurgical and mechanical processing plants. |
||||||||||
|
Data center: Provides cooling water for server rooms. |
||||||||||
|
Payment |
T/T, Western Union. |
|||||||||
|
Service |
Customize and design the size and style according to requirements |
|||||||||
Contact us immediately to discuss your product project requirements
Navigation
Navigation
Contact Us
Tel.: +86 189 3266 2725
E-mail: sale@hbfortis.com
Add.: No.8-1, Zhenxing Street, Matun Town, Zaoqiang County, Hengshui City, Hebei Province
Get in Touch
Get in Touch